Assessment of Wall and Roof Insulation Thickness on HVAC Load Reduction Using HAP Simulation in a Mid-Rise Residential Building in Kabul
DOI:
https://doi.org/10.68924/dprt7t91Keywords:
EPS (Expanded Polystyrene), HAP (Hourly Analysis Program), U-value (Thermal Conductivity Value)Abstract
Kabul's semi-arid continental climate, residential buildings have high heating and cooling energy demands because of poor insulation and envelope performance. In this study, the HVAC load of a typical mid-rise residential building in Ahmad Shah Baba Mena, Kabul, is evaluated in relation to the thickness of the insulation on the roof and the exterior walls.
The Hourly Analysis Program (HAP) was used to simulate four different scenarios: a baseline model without insulation and three cases where Expanded Polystyrene (EPS) insulation was applied to the roof and external walls at thicknesses of 5 cm, 7.5 cm, and 10 cm. With four floors, three conditioned residential levels, and one unconditioned parking level, the case study building has a total conditioned area of 356.7 m².
According to simulation results, thermal insulation dramatically lowers energy use, particularly for heating. In comparison to the uninsulated baseline, heating loads were reduced by roughly 39%, 41%, and 43%, respectively, when 5 cm, 7.5 cm, and 10 cm of EPS insulation were applied to the envelope. Cooling load reductions were less pronounced.
This study provides useful, fact-based advice for maximizing passive envelope performance in Kabul's residential sector by assessing the effects of both wall and roof insulation. The results back up the use of moderate insulation thicknesses (7.5–10 cm) in local building design to strike a balance between cost and energy efficiency.